Work orders and findings
6 record(s)| Date | Order | Notification | Work type | Status | Priority | Discipline | Work centre | Short text | Finding | Action |
|---|---|---|---|---|---|---|---|---|---|---|
| 12 Jul 2026 | 40001618 | 50000842 | Preventive | Planned | High | Mechanical | MECH-48 | Monthly firewater pump skid inspection and run test | Work not yet started. | Inspect package and complete a no-flow automatic-start test. |
| 12 Jun 2026 | 40001491 | 50000792 | Functional Test | Completed | High | Mechanical | MECH-48 | Automatic-start and local run test | Pump started on simulated low-pressure signal. No abnormal vibration or leakage. | Test passed; package returned to automatic mode. |
| 12 May 2026 | 40001234 | 50000694 | Preventive | Completed | High | Mechanical | MECH-48 | Monthly firewater pump skid visual inspection | No visible leakage. Baseframe and supports in good condition. | Inspection completed with no defect raised. |
| 18 Apr 2026 | 40001102 | 50000638 | Inspection | Completed | High | Mechanical | MECH-48 | Auto-start test carried out | Pump started correctly on test signal. No abnormal vibration observed. | No corrective work required. |
| 3 Mar 2026 | 40000987 | 50000597 | Corrective | Completed | Medium | Mechanical | MECH-48 | Coupling guard fasteners tightened | Two fasteners found loose during routine inspection. | Fasteners replaced, torqued and paint-marked. |
| 11 Feb 2026 | 40000841 | 50000521 | Inspection | Completed | Low | Corrosion | INSP-48 | Pump skid paint system checked | Minor coating breakdown on lower skid edge. | Area prepared and touched up; monitor at next inspection. |